Fire terminal board FTI2001-A1
6
Views
45
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
6.2
Views
X3
X400
F201
F202
H
2
0
1
H
1
0
3
H
2
0
3
H
1
0
2
H
2
0
4
H101
H205
H207
H206
S
1
-2
S
1
-1
ON
1
1
1
1
1
1
2
2
H
2
0
2
1
F204
F203
X7
X6
X5
X1
X2
Printed circuit board view FTI2001 fire terminal board
Element
Des.
Function
Plugs and terminals
X1
Supply and message signals from the power supply unit
X2
Not used
X3
Connection to the PMI & mainboard
X5
Supply outputs (2 x 24 V)
X6
Supply input 2 (24 V)
X7
Supply input 1 (24 V)
X400
Connection for the periphery bus
LEDs
H101 … H103 Power Down Ready
H201
Monitoring of the fuse for supply output 1
H202
Monitoring of the fuse for supply output 2
H203
Monitoring of the voltage at supply input 2
H204
Monitoring of the voltage at supply input 1
H207
Monitoring of power supply
H206
Monitoring of voltage surveillance
H205
Monitoring of battery
Fuses
F201
Supply output 1 (1 A/T); Schurter OMT 125
F202
Supply output 2 (1 A/T); Schurter OMT 125
F203
Supply input 1 (2 A/T); Schurter OMT 125
F204
Supply input 2 (2 A/T); Schurter OMT 125
Switch
S1
Switch for supply surveillance of X6 and X7