Periphery board (4 loops) FCI2004-A1
8
Pin assignments
69
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
1
Remote transmission
FAU_… Relay in normal operation = contact 5/4 closed
AL_… Diagram of relay in normal operation = contact 2/3 closed
8.3.5
X6 alarm and fault monitored outputs
Pin
Designation
Description
4
FAU_OUT
Output fault
3
VSYS_O
Supply output for consumer fault
2
AL_OUT-
Alarm output (-)
1
Alarm output (+)
Admissible cable cross-section: 0.2…1.5 mm²
1 Remote transmission
8.3.6
X5 monitored horn outputs 1 and 2
Pin
Designation
Description
4
SOUND2-
Horn output 2 (-)
3
Horn output 2 (+)
2
SOUND1-
Horn output 1 (-)
1
Horn output 1 (+)
Admissible cable cross-section: 0.2…1.5 mm²
+
-
1
2
X5
SOUND2-
F403
+
-
3
4
SOUND1-
2.3 ... 5.5 k
2.3 ... 5.5 k
F400