3
Power supply (70 W) FP2001-A1
Indicators
24
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
3.3.2
X2 monitoring signals
Pin
Designation
Description
8
Battery
Detection line (#BATT): Battery fault
7
Convert
Detection line (#CONV): Power supply fault
6
Main
Detection line (#MAINS): Mains fault
5
Common GND
Ground (COMMON)
4
Usys +
System supply (VSYS+)
3
Usys –
System supply (VSYS-)
2
Akku +
Battery supply (+)
1
Akku –
Battery supply (–)
Admissible cable cross-section: 0.2…2.5 mm²
7
8
5
6
X2
3
4
Main
Common GND
Akku +
VSYS-
VSYS+
Convert
Battery
2
1
-
+
Usys +
-
+
Usys -
Akku -
#BATT
#CONV
#MAINS
COMMON
1
F103
F102
1 Cable tree to periphery board or fire terminal board
See also
X1 supply [ 46]
X1 supply [ 70]
X1 supply [ 57]
3.4
Indicators
LED
Color
Function
Condition
Meaning
MAINS
(H202)
Yellow
Monitoring of
voltage surveillance
On
No mains voltage, fault in the primary supply
Off
Normal condition
BATT
(H201)
Yellow Monitoring of battery On
Battery fault
Off
Normal condition
CONV
(H200)
Green
Monitoring of power
supply
On
Normal condition
Off
Power supply fault