Periphery board (2 loops) FCI2002-A1
7
Description
51
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
7
Periphery board (2 loops) FCI2002-A1
7.1
Description
The periphery board (2 loops) is used in the fire control panel FC2020. It has the
following features:
1 integrated line card for the connection of 2 FDnet loops or 4 stubs (mixed
variants are possible)
Maximum of 252 device addresses per loop
Maximum of 252 device addresses per integrated line card
Optional loop extension (FDnet) FCI2003-A1 to extend to 4 loops or 8 stubs
Connections for one remote transmission device each for RT Alarm and RT
Fault
One monitored output each for Alarm and Fault
Eight configurable inputs/outputs (24 V)
Monitored sounder (horn) output
Two monitored supply outputs
Input for a third supply source
Activation of fault outputs in degraded mode operation
Alarm evaluation in degraded mode operation; activation of the alarm and horn
outputs in case of emergency alarm