Periphery board (4 loops) FCI2004-A1
8
Technical data
75
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
Configurable inputs/outputs
1…12
Designation
'I/O1' … 'I/O12'
Individually configurable as
Input
Output
Configured as input
Design
Digital
Not monitored
Threshold values
> Vsys/2 = off
< Vsys/4 = on
Configured as output:
Design
Open drain
Inherently short-circuit-proof
Excess temperature protection
Output voltage
DC 21…28.6 V
Output current per output
Max. 300 mA
Output current of all outputs (total)
1.5 A
Connection terminals
Inputs, outputs and FDnet
Design
Screw terminals
Admissible cable cross-section
0.2…1.5 mm²
Supply
Design
Screw terminals
Admissible cable cross-section
0.5…2.5 mm²
Mechanical data
Dimensions (L x W x H)
210 x 225 x 40 mm
Weight
350 g
1
Some voltage ranges of certified horns are limited to 28 V. This maximum voltage
can only be guaranteed if the control panel temperature is >5 °C.