Basic Parameter Group 01
PARAMETER DESCRIPTION 69
5.2.7
JOG run
The frequency and acceleration/deceleration time for JOG running can be set. JOG can be used for conveyor
positioning, test run, etc.
Parameter
Name
Default
Setting Range
Content
01-13
P.15
JOG frequency
5.00Hz
0~599.00Hz
---
01-14
P.16
JOG Acc/ Dec
time
0.50s
0~360.00s/
0~3600.0s
01-08(P.21)=0/
01-08(P.21)=1
JOG operation
In JOG mode, the output frequency is the set value of 01-13(P.15), and the acceleration / deceleration time is the
set value of 01-14(P.16).
Time
Output frequency
01-09(P.20)
01-03(P.15)
01-09(P.20)
01-03(P.15)
Forward
01-14
(P.16)
Reverse
01-14
(P.16)
O N
O N
Button
Button
Note:1. Please refer to Section 4.3.3 for how to enter the JOG mode.
2.
For the operation steps of switching between forward and reverse rotation, please refer to 4.2.7 Operation flow
chart for changing motor rotation direction.
5.2.8
Output frequency filter time
This filter can reduce the impact when switching the frequency between high and low, and thus reduce the
vibration of machine
Parameter
Name
Default
Setting Range
Content
01-15
P.28
Output frequency filter
time
0
0~31
---
Output frequency filter time
The filtering effect is better when output frequency filter time is larger, but will also increase the response delay.
If 01-15(P.28) is set to 0, the filtering function is off.