Communication parameter group 07
PARAMETER DESCRIPTION 118
Step 1: Use upper controller to send FA command in Format A:
ENQ
Inverter station
number 0
Code
HFA
Waiting time
Data
H0000
Check code
Sum Check
CR
H05
H30 H30
H46 H41
H30
H30 H30 H30 H30
H44 H37
H0D
Step 2: After receive and processing the data without error, inverter will send reply to upper controller in Format C:
ACK
Inverter station
number 0
CR
H06
H30 H30
H0D
Example 3. Upper controller reads the value of 01-28(P.162):
Step1: Upper controller sends write and page change command, using Format A:
ENQ
Inverter station
number 0
Code
HFF
Waiting time
Data
H0001
Check code
Sum Check
CR
H05
H30 H30
H46 H46
H30
H30 H30 H30 H31
H44 H44
H0D
P.162 is on page 1
Step 2: After receive and processing the data without error, inverter will send reply to upper controller in Format C:
ACK
Inverter station
number 0
CR
H06
H30 H30
H0D
Step 3: Upper controller requests inverter for reading 01-28(P.162) value using Format B:
ENQ
Inverter station number
0
Code
H3E
Waiting time
Check code
Sum Check
CR
H05
H30 H30
H33 H45
H30
H30 H38
H0D
Subtract 100 from 162 (=62),convert 62 to H3E in hex,then convert E to H33、H45 in ASCII
Step 4: Once inverter receives and processes the data without error, 01-28(P.162) value will be sent to upper
controller in Format E:
STX
Inverter station
number 0
Read out data
HFFFF
Unit
ETX
Check data
Sum Check
CR
H02
H30 H30
H46 H46 H46 H46
H32
H03
H41 H41
H0D
Example 4. Change the content of 01-28(P.162) to 50 (Default setting is 99999).
Step 1~2 are the same as Step 1~2 of Example 3;
Step 3: Upper controller requests inverter to write 50 in 01-28(P.162) in Format A:
ENQ
Inverter station
number 0
Reference
code HBE
Waiting time
Data
H1388
Check code
Sum Check
CR
H05
H30 H30
H42 H45
H30
H31 H33 H38 H38
H45 H42
H0D
Subtract 100 from 162(=62), minimum unit of 01-28 is 0.01, hence 50×100=5000,
Convert 62 to H3E in hex, then convert 5000 to H1388 in hex,
H3E+H80=HBE then convert 1、3、8、8 to ASCII for transmission
Step 4: After receive and processing the data without error, inverter will send reply to upper controller in Format C: