Application parameter group 10
PARAMETER DESCRIPTION 141
5.10.5 Remote setting function selection
If operation box is located away from control cabinet, without analog signal, variable speed can still be realized
through digital input.
Parameter
Name
Default Setting Range
Content
10-11
P.61
Remote
control
function
0
0
0: Off
X1
Remote control function, frequency save in memory
X2
Remote control function, frequency won’t save
X3
Remote control function, frequency won’t save, clear
frequency setting every time STF/STR “turn off”.
X4
Remote control function, frequency save in memory every 5s
1X
Frequency command range 01-01(P.2)~01-00(P.1),
frequency command value from RH,RM setting
Remote setting function
In external mode, combined mode 1,combined mode 5, use digital input to change output frequency.
Acceleration
(
RH
)
Deceleration
(
RM
)
Clear
(
RL
)
Run forward
(
STF
)
ON
ON
ON
ON
ON
ON
ON
ON
ON
Power
Output
frequency
(
Hz
)
0
Time
*
When 10-11(P.61)=0X target frequency is set by exterior signal(except multi-speed) or set
in PU mode, name as main target frequency.
When 10-11(P.61)=1X it is 01-01: minimum frequency.
10-11(P.61)=X1/X2/X4
10-11(P.61)=X3
10-11(P.61)=X2/X3
10-11(P.61)=X1/X4
Remote function setting
1.
10-11(P.61) decides remote function and ways to save frequency.
Set 10-11(P.61)=X1~X4(remote control function on),terminal RM, RH, RL will be accelerate (RH),
decelerate (RM) and clear (RH).See following figure:
Inverter
Forward
Acceleration
Deceleration
Clear
STF
RH
RL
RM
SD
10
3
5
2.
If 10-11 (P.61)=1~4, the target frequency of inverter = (frequency set during RH and RM ope external
Setting