Digital input/ output parameter group 03
PARAMETER DESCRIPTION 86
Group
Parameter
Number
Name
Setting Range
Default Page
03-00
P.83
Terminal STF input
function
37~38:Reserved
0
39: STF/STR +STOP (Use with RUN signal, when ON,
motor runs reverse, when OFF, motor stops then runs
forward.)
40: P_MRS (Stops inverter output immediately by pulse
signal input)
41: PWM set frequency
(Only valid with terminal STF
and parameter 03-00(P.83))
42:Reserved
43: RUN_EN (Enable digital input terminal operation)
44: PID_OFF (Enable digital input terminal turning off
PID)
45: Second frequency command source mode
03-01
P.84
Terminal STR input
function
Same as 03-00
1
03-03
P.80
Terminal M0 input
function
Same as 03-00
2
03-04
P.81
Terminal M1 input
function
Same as 03-00
3
03-11
P.85
Terminal A-C output
function
0: RUN(Output when inverter running)
5
1: SU(Output when reach target frequency)
2: FU(Output when reach 03-21 03-22 value )
3: OL(Output when overload)
4: OMD(Output when output current is zero)
5: ALARM(Output when alarm)
6: PO1(Output when in program operation step)
7: PO2(Output when in program operation cycle)
8: PO3(Output when in program operation pause)
9~10:Reserved
11:OMD1(Output when output current is zero 1)
12 :OL2(Output when over torque)
13~16:Reserved
17: RY(Output when inverter is powered on and no
alarm)
18: Output when it’s time for maintenance
41: Output when PID feedback signal disconnect
03-14
P.87
Digital input logic
0~15
0
03-15
P.88
Digital output logic
0:Terminal A-C output positive logic
0
2:Terminal A-C output negative logic
03-16
P.120
Output signal delay time
0~3600.0s
0.0s
03-17
P.157
Digital input terminal filter
time
0~2000
4