
Protection parameter group 06
PARAMETER DESCRIPTION 111
5.7.6
Input phase loss protection
Turn on input phase failure protection
Parameter
Name
Default Setting Range
Content
06-13
P.281
Input phase loss
protection
0
0
Off
1
When input phase loss, built-in keypad shows IPF alarm and
inverter stops
Input phase loss protection
When 06-13(P.281)=1, input phase loss protection is on; when input power is out of phase or three phases are
imbalance, inverter will trigger alarm IPF.
5.7.7 Time record function
It is used to record the inverter accumulative operation time.
Parameter
Name
Default Setting Range
Content
06-27
P.292
Total inverter operation
time (minutes)
0 min
0~1439min
---
06-28
P.293
Total inverter operation
time (days)
0 day
0~9999day
---
06-29
P.296
Total inverter power on
time (minutes)
0 min
0~1439min
---
06-30
P.297
Total inverter power on
time (days)
0 day
0~9999day
---
Time record function
06-27(P.292)/06-29(P.296)
is operation minutes of the inverter. The value cannot be changed when 00-02=3
(P.998=1) is executed or power is cut off, but can be cleared when set 06-27(P.292)/06-29(P.296) to 0.
06-28(P.293)/06-30(P.297)
is operation days of the inverter. The value cannot be changed when 00-02=3
(P.998=1)
is executed or power is cut off, but can be cleared when set 06-28(P.293)/06-30(P.297) to 0.
Setting
Setting
Содержание SL3 Series
Страница 2: ......
Страница 107: ......
Страница 200: ...Appendix 4 Optional equipment Appendix 196 ...
Страница 209: ...Appendix 5 European Specification Compatibility Description Appendix 205 3 CE Self Declaration ...
Страница 210: ...Appendix 5 European Specification Compatibility Description Appendix 206 ...