Application parameter group 10
PARAMETER DESCRIPTION 149
SD
STF
STR
M1
M0
R
S
AC~
380V
U
V
W
Motor
T
Start button
Stop button
Left limit
switch
Right limit
switch
K1
K3
K2
K4
System wiring diagram
Please wire according to the above diagram, connect a limit switch between M0 and SD, M1 and SD, and connect
a pulse switch between STF and SD, STR and SD.
Power on the inverter, execute parameter 00-02=3 (P.998=1), set parameter 10-55 (P.226) to 1, turn on
reciprocating machine function. The multi-function terminal settings are all factory settings no need to change
value. If target frequency is given by external terminal, the M0 and M1 terminals will affect the target frequency, so
please set the value of 04-01 (P.5) and 04-02 (P.6) to the same as target frequency .
When K3 and K4 are both in off state, press K1 and inverter forward turn to trigger K3 once, then inverter reverse
turn to trigger K4 once and then turn forward, reciprocating. If press K2 the system stops running.
When K3 (or K4) is
in off state, press K1 and it will reverse (or forward) until trigger K4 (or K3) once and then
forward (or reverse). If press K2 the system stops running.
To prevent dangerous situations caused by the failure of the limit switch, additional one-way running time:
reciprocating forward/reverse limit time is added. Two limit switches are not allowed to be closed at the same time.
If they are closed at the same time, the system will stop running.
Forward
Reverse
K3 left limit
switch
K4 right limit
switch
Operation diagram