Appendix 1 Parameter table
Appendix 165
Parameter
Number
Group
Name
Setting Range
Default Page
P.85
03-11
Terminal A-C output
function
4: OMD(Output when output current is zero)
5
5: ALARM(Output when alarm)
6: PO1(Output when in program operation step)
7: PO2(Output when in program operation cycle)
8: PO3(Output when in program operation pause)
9:Reserved
10:Reserved
11:OMD1(Output when output current is zero 1)
12 :OL2(Output when over torque)
13~16:Reserved
17: RY(Output when inverter is powered on and no
alarm)
18: Output when it’s time for maintenance
41: Output when PID feedback signal disconnect
P.87
03-14
Digital input logic
0~15
0
P.88
03-15
Digital output logic
0:Terminal A-C output positive logic
0
2:Terminal A-C output negative logic
P.89
13-00
Slip compensation
coefficient
0~10
0
P.90
00-00
Inverter model
Read only
Read
only
P.91
01-16
Frequency jump 1A
0~599.00Hz
99999
99999: Off
P.92
01-17
Frequency jump 1B
0~599.00Hz
99999
99999: Off
P.93
01-18
Frequency jump 2A
0~599.00Hz
99999
99999: Off
P.94
01-19
Frequency jump 2B
0~599.00Hz
99999
99999: Off
P.95
01-20
Frequency jump 3A
0~599.00Hz
99999
99999: Off
P.96
01-21
Frequency jump 3B
0~599.00Hz
99999
99999: Off
P.97
00-17
Second target frequency
selection
0: Frequency set by built-in keypad
0
1: Frequency set by RS485 communication
2: Frequency set by analog input
P.98
01-26
Middle frequency 1
0~599.00Hz
3.00Hz
P.99
01-27
Output voltage 1 of middle
frequency
0~100.0%
10.0%
P.100
04-15
Programmed operation
minute / second selection
0: Select minute as the time increment.
1
1: Select second as the time increment.