System parameter group 00
PARAMETER DESCRIPTION 56
5.1.9 Forward/reverse rotate prevent function
Set this parameter to limit the motor rotation to only one direction, and prevent reverse rotation fault resulting from
the incorrect input of the start signal.
Parameter
Name
Default
Setting Range
Content
00-15
P.78
Prevent forward/
reverse rotation
selection
0
0
Forward/reverse rotation are both permitted.
1
Prevent reverse rotation (Giving reverse signal decelerates
and stops the motor).
2
Prevent forward rotation (Giving forward signal decelerates
and stops the motor).
Note: It is valid to all start signals.
5.1.10 Operation mode selection
Select the operation mode of the inverter, and determine the source of start signal and target frequency.
Parameter
Name
Default Setting Range
Content
00-16
P.79
Operation mode
selection
0
0
“PU mode”, “external mode” and “Jog mode” are
interchangeable.
1
“PU mode” and “JOG mode” are interchangeable.
2
“External mode” only
3
“Communication mode” only
4
“Combined mode 1”
5
“Combined mode 2”
6
“Combined mode 3”
7
“Combined mode 4”
8
“Combined mode 5”
00-17
P.97
Second target
frequency selection
0
0
Frequency set by built-in keypad
1
Frequency set by RS485 communication
2
Frequency set by analog input
00-19
P.35
Communication
mode selection
0
0
In communication mode, run signal and frequency is given by
communication.
1
In communication mode, run signal and frequency is given by
external signal.
Operation mode selection
Please refer to Section 4.3 for detailed setting and usage
Communication mode instruction selection
When 00-16(P.79)=3, select communication mode:
1.
If 00-19(P.35)=0, Start and frequency command is given by communication;
2.
If 00-19(P.35)=1, Start and frequency command is given by external terminals.
Setting
Setting
Содержание SL3 Series
Страница 2: ......
Страница 107: ......
Страница 200: ...Appendix 4 Optional equipment Appendix 196 ...
Страница 209: ...Appendix 5 European Specification Compatibility Description Appendix 205 3 CE Self Declaration ...
Страница 210: ...Appendix 5 European Specification Compatibility Description Appendix 206 ...