Digital input/ output parameter group 03
PARAMETER DESCRIPTION 90
2)
Two-wire control mode 2:
K0
K1
RUN(03-0X(P.8X)=28)
STF/STR(03-0X(P.8X)=29)
SD
K0
K1
Run
command
0
1
0
1
1
1
0
0
Stop
Forward
Reverse
Stop
3)
Three-wire control mode 1 (with seal-in function): K0 is STOP, normal close. When trigger inverter will stop.
K1 is forward and K2 is reverse, normal open. All K0 K1 K2 are edge trigger button.
STOP(03-0X(P.8X)=31)
K0
K2
K1
STR(03-0X(P.8X)=1)
STF(03-0X(P.8X)=0)
SD
4)
Three-wire control mode 2 (with seal-in function): K1 is STOP, normal close. When trigger inverter will stop. K2
is RUN, normal open. K1 K2 are edge trigger buttons. Change direction by STF/STR terminal, set value: 39.
When changing the direction, stop the inverter first, then switch K0 state and start inverter again.
STOP(03-0X
(
P.8X
)
=31)
K0
K2
K1
STF/STR(03-0X
(
P.8X
)
=29)
RUN(03-0X
(
P.8X
)
=28)
Run
command
Forward
Reverse
SD
K0
1
0