Application parameter group 10
PARAMETER DESCRIPTION 142
set frequency other than multi-speed/PU set frequency);
If 10-11 (P.61)=11~14, the target frequency of inverter = frequency set during RH and RM operation.
Frequency save
The frequency save function is to store the remote function frequency (the frequency set by RH, RM operation) in
the memory (EEPROM), once the power is turned off then restart, inverter will run to
frequency save value (10-11
(P.61) = X1/X4).
<
Frequency save memory condition >
10-11(P.61)=X1
1.
The frequency when start signal (STF/STR) is "off";
2.
When RH (acceleration) and RM (deceleration) are both "off", the remote control setting frequency is stored
every 1 minute (If RL is triggered will not write);
10-11(P.61)=X4
1. The frequency when RH (acceleration) and RM (deceleration) signals are both "off";
2. Store the remote control setting frequency once every 5s (If RL is triggered will not write);