Appendix 1 Parameter table
Appendix 185
Group
Parameter
Number
Name
Setting Range
Default Page
06-17
P.261
Maintenance alarm
function
0: Off
0
1~9998day: Used to set the time for maintenance
alarm output signal
06-18
P.280
Short circuit protection
function
X0: Turn off short circuit to ground detect when inverter
start
10
X1: Short circuit to ground detect when inverter start
0X: Turn off output short circuit,
1X: When output short circuit, built-in keypad shows
SCP alarm and inverter stops
06-27
P.292
Total inverter operation
time (minutes)
0~1439 min
0min
06-28
P.293
Total inverter operation
time (days)
0~9999 day
0day
06-29
P.296
Total inverter power on
time (minutes)
0~1439min
0min
06-30
P.297
Total inverter power on
time (days)
0~9999day
0day
06-40
P.288
Alarm record code query
Choose 0~12 recorded alarm
0
06-41
P.289
Alarm record code
display
Read only
Read
only
06-42
P.290
Alarm record message
query
Choose 0~10 recorded alarm
0
06-43
P.291
Alarm record message
display
Read only
Read
only
07-00
P.33
Communication protocol
selection
0:Modbus protocol
1
1:Shihlin protocol
07-01
P.36
Inverter communication
station number
0~254
0
07-02
P.32
Serial communication
baud rate
0:baud rate :4800bps
1
1:baud rate :9600bps
2:baud rate :19200bps
3:baud rate :38400bps
07-03
P.48
Data length
0:8bit
0
1:7bit
07-04
P.49
Stop bit length
0:1bit
0
1:2bit
07-05
P.50
Parity check selection
0:No parity check
0
1:Odd
2:Even
07-06
P.51
CR/LF selection
1:CR only
1
2:Both CR and LF