Digital input/ output parameter group 03
PARAMETER DESCRIPTION 89
Parameter
Name
Default Setting Range
Content
03-00
P.83
Terminal STF input
function
0
36
TRI(Triangle wave function)
37
Reserved
38
Reserved
39
STF/STR +STOP (Use with RUN signal, when ON, motor
runs reverse, when OFF, motor stops then runs forward.)
40
P_MRS (Stops inverter output immediately by pulse signal
input)
41
PWM set frequency (Only valid with terminal STF and
parameter 03-00(P.83))
42
Reserved
43
RUN_EN (Enable digital input terminal operation)
44
PID_OFF (Enable digital input terminal turning off PID)
45
Second frequency command source mode
03-01
P.84
Terminal STR input
function
1
Same as 03-00
Same as 03-00
03-03
P.80
Terminal M0 input
function
2
Same as 03-00
Same as 03-00
03-04
P.81
Terminal M1 input
function
3
Same as 03-00
Same as 03-00
Digital input terminals function selection
At default, 03-03(P.80)=2(RL),03-04(P.81)=3(RM),03-00(P.83)=0(STF),03-01(P.84)=1(STR).
Changing 03-01(P.84)、03-03(P.80)
settings change the function of the terminals. For example, 03-03(P.80)=2
means that M0 terminal acts as RL. If 03-03(P.80) is set to 8, M0 terminal function will change to RT, which will act
as “second function”. Another example, 03-00(P.83)=0 means that STF terminal serves as “inverter runs forward”
function, and if change 03-00(P.83) to 6, STF terminal function will change to OH, which will serve as the input
terminal of external thermal relay.
Set value:6 OH(External thermal relay):
Old motors usually come with thermal relay attached to the front of the motor to prevent motor from overheating.
When external thermal relay actuate, inverter will alarm and show “OHT”.
Four different wiring techniques (1 means ON, 0 means Off, and X = 0,1,3,4)
1)
Two-wire control mode 1:
K0
K1
STF(03-0X(P.8X)=0)
STR(03-0X(P.8X)=1)
SD
K0
K1
Run
command
0
1
0
1
1
1
0
0
Stop
Forward
Reverse
Stop
Setting