5-11
Fault display
How to monitor a fault condition in the Drive group
Frequency
Current
During
Accel
Drive group
STOP
RESET
Over-
current
trip
1
-. This message appears when an Overcurrent fault occurs.
-. Press the Enter (
) key or UP/Down key once.
2
-. The
run frequency
at the time of fault (30.0) is displayed.
-. Press the Up (
) key once.
3
-. The
output current
at the time of fault is displayed.
-. Press the Up (
) key once.
4
-. Operating status is displayed. A fault occurred during acceleration.
-. Press the STOP/RST key once.
5
-. A fault condition is cleared and “nOn” is displayed.
When more than one fault occurs at the same time
Drive group
Over
current
Over
voltage
Motor
overheat
-. Maximum three faults information is
displayed as shown left.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...