7-6
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
F30
[V/F pattern]
0 ~ 2
0
{Linear}
0
X
1
{Square}
2
{User V/F}
F31
1)
[User V/F
frequency 1]
0 ~ 400
[Hz]
It is used only when V/F pattern is set to
2(User V/F).
It cannot be set above F21 – [Max
frequency].
The value of voltage is set in percent of
H70 – [Motor rated voltage].
The values of the lower-numbered
parameters cannot be set above those
of higher-numbered.
15.00
X
F32
1)
[User V/F
voltage 1]
0 ~ 100
[%]
25
X
F33
1)
[User V/F
frequency 2]
0 ~ 400
[Hz]
30.00
X
F34
1)
[User V/F
voltage 2]
0 ~ 100
[%]
50
X
F35
1)
[User V/F
frequency 3]
0 ~ 400
[Hz]
45.00
X
F36
1)
[User V/F
voltage 3]
0 ~ 100
[%]
75
X
F37
1)
[User V/F
frequency 4]
0 ~ 400
[Hz]
60.00
X
F38
1)
[User V/F
voltage 4]
0 ~ 100
[%]
100
X
F39
[Output voltage
adjustment]
40 ~ 110
[%]
This parameter adjusts the amount of
output voltage.
The set value is the percentage of input
voltage.
100
X
F40
[Energy-saving
level]
0 ~ 30
[%]
This parameter decreases output
voltage according to load status.
0
0
F50
[Electronic
thermal
select]
0 ~ 1
This parameter is activated when the
motor is overheated (time-inverse).
1
0
F51
2)
[Electronic
thermal level
for 1 minute]
50 ~ 200
[%]
This parameter sets max current
capable of flowing to the motor
continuously for 1 minute.
The set value is the percentage of H33
– [Motor rated current].
It cannot be set below F52 –[Electronic
thermal level for continuous].
150
0
F52
2)
[Electronic
thermal level
for continuous]
This parameter sets the max motor
current for continuous operation.
It cannot be set higher than F51 –
[Electronic thermal level for 1 minute].
100
0
1)
: Set F30 to 2(User V/F) to display this parameter.
2)
: Set F50 to 1 to display this parameter.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...