10-40
10.20 DRAW Control
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
Group 1
F70
DRAW mode select
-
0 ~ 3
0
-
F71
DRAW rate
-
0.0 ~ 100.0
0.0
%
Draw control is a sort of Open Loop tension control. Draw is the ratio of speed difference
between one roll and the other. Tension is generated as in the following equations:
Where
V1, V2: Transfer speed of each roll (m/min)
T: Tension (kg)
E: Elasticity coefficient of processed material (kg/mm
2
)
S: Sectional area of processed material (mm
2
)
The rate reflected in the output frequency differs according to the selection of F70 (DRAW mode select)
F70
Draw
Operation
0 Draw not operated
1 V1(0~10V) input
2 I(0~20mA) input
3 V1(–10~10V) input