3-5
Opening to access
Ground Terminal
WARNING
Use the Type 3 grounding method (Ground impedance: Below 100
Ω
) for 2S/T class
inverters.
Use the Special Type 3 grounding method (Ground impedance: Below 10
Ω
) for 4T class
inverters.
Use the dedicated ground terminal to ground the inverter. Do not use the screw in the case
or chassis, etc for grounding.
☞
Note : Grounding procedure
1) Remove the front cover.
2) Connect the Grounding wire to the ground terminal through the opening for ground
terminal as shown above. Enter the screw driver from vertical to the terminal and
secure the screw tightly.
☞
N
ote : Grounding work guidance
Inverter
capacity
2S/T Class (1/3 phase 200-230Vac)
4T Class (3 phase 380-480Vac)
Wire size
Terminal
screw
Grounding
method
Wire size
Terminal
screw
Grounding
method
0.4~4.0 kW
4 mm
2
M3
Type 3
2.5 mm
2
M3
Special
Type 3
5.5~7.5 kW
6 mm
2
M4
4 mm
2
M4
11 ~ 15 kW
16 mm
2
M5
6 mm
2
M5
18.5~22 kW
25 mm
2
M6
16 mm
2
M5
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...