7-7
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
F53
2)
[Motor cooling
method]
0 ~ 1
0
Standard motor having cooling
fan directly connected to the
shaft
0
0
1
A motor using a separate motor
to power a cooling fan.
F54
[Overload
warning level]
30 ~ 150
[%]
This parameter sets the amount of
current to issue an alarm signal to the
relay or multi-function output terminal
(see I54, I55).
The set value is a percentage of H33-
[Motor rated current].
150
0
F55
[Overload
warning time]
0 ~ 30
[Sec]
Delay time of the current level set in
F54- [Overload warning level]
10
0
F56
[Overload trip
select]
0 ~ 1
This parameter turns off the inverter
output when motor is overloaded.
1
0
F57
[Overload trip
level]
30 ~ 200
[%]
This parameter sets the amount of
overload current.
The value is the percentage of H33-
[Motor rated current].
180
0
F58
[Overload trip
time]
0 ~ 60
[Sec]
This parameter turns off the inverter
when the current greater than F57-
[Overload trip level] flows to the motor
for F58- [Overload trip time].
60
0
2)
: Set F50 to 1 to display this parameter.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...