10-36
FX
Output Freq.
1
2
30.00
Communication FX
P8 : 2nd Change
3
4
5
①
Accelerate for accel time up to setting frequency by Drive 1 mode, FX signal.
②
Drive continuously under FX is ON because DRV2 is 1 when P8 terminal input is ON and
change into 2
nd
.
③
Stop gradually as stop command because DRV is communication drive when P8 terminal
input is OFF and change into 1st.
④
Accelerate up to setting frequency for Drive 1 mode, FX signal is ON.
⑤
Stop gradually under FX is OFF because DRV2 is 1 when P8 terminal input is ON and
change into 2
nd
.
CAUTION
If you press ON while multi-function input terminal (P1 ~ P8) is set to 2
nd
Source,
frequency command and drive command is changed to Drive mode 2. So you
should check Drive mode 2 before configuring the multi-function terminal.