9-11
Power On Start select
Group
Code Parameter Name
Setting Range
Initial
Unit
Drive group
drv
[Drive mode]
1, 2
0 ~ 3
1
Function group 2
H20
[Power On Start select] 1
0 ~ 1
0
Set H20 to 1.
When AC input power is applied to the inverter with drv set to 1 or 2 {Run via control
terminal and one of them ON), motor starts acceleration.
This parameter is inactive when
drv
is set to 0 {Run via keypad} or 3 {RS485
communication}.
CAUTION
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly upon applying AC input power.
Run
command
Frequency
Input voltage
When H20 is 0
When H20 is 1
Restart after fault reset
Group
Code Parameter Name
Setting Range Initial
Unit
Drive group
drv
[Drive mode]
1, 2
0 ~ 3
1
Function group 2
H21 [Restart after fault reset
selection]
1
0 ~ 1
0
Set H21 to 1.
Motor starts acceleration if
drv
is set to 1 or 2 and the selected terminal is ON when a fault
is cleared.
This parameter is inactive when
drv
is set to 0 {Run via keypad} or 3 {RS485
communication}.
CAUTION
Particular attention must be directed to this function due to potential hazard as motor starts to
run suddenly after the fault is cleared.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...