11-7
11.4 Analog Output
Group
Display
Parameter Name
Setting
Range
Default Unit
I/O group
I50
[Analog output item select] -
0 ~ 3
0
I51
[Analog output level
adjustment]
-
10 ~ 200 100
%
Output item and the level from the AM terminal are selectable and adjustable.
I50: The selected item will be output on the Analog output terminal (AM).
I50
Analog output
item select
Item corresponding to 10V
200V
400V
0
Output frequency.
Max Frequency (F21)
1
Output current
150% of Inverter rated
current
2
Output voltage
282Vac
564Vac
3
Inverter DC link
voltage
400Vdc
800Vdc
I51: If you want to use Analog output value as an input signal for instruments, the value can be
adjustable according to instruments specifications.
AM
CM
0 ~ 10Vdc
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...