12-7
12.6 Inverter Overload
Group Code Parameter
Set
Range
Initial
Unit
I/O
group
I54
[Multi-function output terminal
select]
6
0 ~ 18
12
I55
[Multi-function relay select]
6
17
Inverter overload prevention function is activated when the current is above inverter rated current.
Multi-function output terminal (MO) or Multi-function relay (3ABC) is used as the alarm signal output
during inverter overload trip.
12.7 Frequency command loss
Group Code Parameter
Set
Range
Initial Unit
I/O
group
I16
[Criteria for analog input signal
loss]
0
0 ~ 2
0
I62
[Drive mode select after loss of
frequency command]
-
0 ~ 2
0
I63
[Wait time after loss of
frequency command]
-
0.1 ~ 120 1.0
sec
I54
[Multi-function output terminal
select]
11
0 ~ 18
12
I55
[Multi-function relay select]
11
17
Select the Drive mode when frequency reference set via Analog (V1, I) input terminal or
communication option is lost.
I16: This is to set the criteria for analog input signal loss.
I16
[Criteria for analog
input signal loss]
0
Disabled (Does not check the analog input
signal loss)
1
When half the value set in I2, I7, I12 is
entered
2
When less than the value set in I2, I7, I12 is
entered
Ex 1) The inverter determines the freq reference is lost when DRV- Frq is set to 3 (Analog
V1 input), I16 to 1 and analog input signal is less than half the value set in I7.
Ex 2) The inverter determines the freq reference is lost when DRV- Frq is set to 6 (V1+I),
I16 to 2 and V1 input signal is either below the value set in I7 or I input value is less than
the I12 value.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...