9-21
9.7 Frequency limit
Frequency limit using Max Frequency and Start Frequency
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Function
group 1
F21
[Max frequency]
-
0 ~ 400
50.00
Hz
F23
[Start frequency]
-
0.1 ~ 10
0.50
Hz
Max Frequency: Frequency highest limit. Any frequency cannot be set above [Max
frequency] except for F22 [Base frequency].
Start Frequency: Frequency lowest limit. Until a frequency reference is set lower than this,
0.00 output frequency is automatically set.
Frequency command limit using High/Low limit
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Function
group 1
F24
[Frequency
high/low
limit select]
1
0 ~ 1
0
F25
[Frequency high limit]
-
0 ~ 400
50.00
Hz
F26
[Frequency low limit]
-
0 ~ 400
0.50
Hz
Set F24 to 1.
Active run frequency can be set within the range of F25 and F26.
When frequency setting is done via Analog input (voltage or current input), the inverter operates within
the range of high and low limit frequency as shown below.
This setting is also valid when frequency setting is done via keypad.
Freq.
V1(Voltage input)
Max freq.
0
20mA
10V
I (Current input)
High limit
freq.
Low limit
freq.
When freq. limit is not
selected
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...