7-21
LED
display
Parameter name
Min/Max
range
Description
Factory
default
Adj.
during
run
I51
[Analog output
level adjustment]
10~200
[%]
Based on 10V.
100
O
I52
[Frequency
detection level]
0 ~ 400
[Hz]
Used when I54 or I55 is set to 0-4.
Cannot be set higher than F21.
30.00
O
I53
[Frequency
detection
bandwidth]
10.00
O
I54
[Multi-function
output terminal
select]
0 ~ 19
0
FDT-1
12
O
1
FDT-2
I55
[Multi-function
relay select]
2
FDT-3
17
3
FDT-4
4
FDT-5
5
Overload (OLt)
6
Inverter Overload (IOLt)
7
Motor stall (STALL)
8
Over voltage trip (Ovt)
9
Low voltage trip (Lvt)
10 Inverter Overheat (OHt)
11 Command loss
12 During Run
13 During Stop
14 During constant run
15 During speed searching
16 Wait time for run signal input
17 Fault output
18 Warning for cooling fan trip
19 Brake signal selection
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...