12-8
I62: When no frequency command is given for the time set in I63, set the drive mode as the table below.
I62
[Drive mode select
after loss of
frequency command]
0
Continuous operation with the
frequency before command loss
occurs
1
Free run stop (Coast to stop)
2
Deceleration ramp to stop
I54, I55: Multi-function output terminal (MO) or Multi-function relay output (3ABC) is used to output
information on loss of frequency command to external sequence.
Ex) when I16 is set to 2, I62 to 2, I63 to 5.0 sec and I54 to 11, respectively,
Freq
MO
Run
command
Set
freq
5sec