9-19
Manual torque boost
Group
Code Parameter Name
Setting Range Initial
Unit
Function
group 1
F27
[Torque Boost select]
0
0 ~ 1
0
F28
[Torque boost in forward direction]
-
0 ~ 15
2
%
F29
[Torque boost in reverse direction]
Set F27 to 0 {Manual torque boost}.
The values of [Torque boost in forward/reverse direction] are set separately in F28 and
F29.
CAUTION
If the boost value is set much higher than required, it may cause motor overheating or
inverter trips, due to over-energizing.
Auto torque boost
Group
Code Parameter Name
Setting Range
Initial
Unit
Function group 1
F27
[Torque Boost select]
1
0 ~ 1
0
Function group 2 H34
[No
load
motor
Current]
-
0.1 ~ 20
-
A
H41
[Auto tuning]
0
0 ~ 1
0
H42
[Stator resistance (Rs)] -
0 ~ 14
-
Ω
Before set Auto Torque Boost, H34 and H42 should be set correctly.
Select 1{Auto torque boost} in F27.
Inverter automatically calculates torque boost value using motor parameters and outputs
the corresponding voltage.
FX
Time
RX
Voltage
FX torque
boost
No torque boost
100%
RX torque
boost
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...