7-11
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
H19
[Input/output
phase loss
protection
select]
0 ~ 3
Input phase
protection
Output phase
protection
0
O
Bit 1
Bit 0
0
-
-
1
-
2
-
3
H20
[Power On
Start select]
0 ~ 1
This parameter is activated when drv is set
to 1 or 2 (Run/Stop via Control terminal).
Motor starts acceleration after AC power is
applied while FX or RX terminal is ON.
0
O
H21
[Restart
after fault
reset
selection]
0 ~1
This parameter is activated when drv is set
to 1 or 2 (Run/Stop via Control terminal).
Motor accelerates after the fault condition is
reset while the FX or RX terminal is ON.
0
O
H22
1)
[Speed
Search
Select]
0 ~ 15
This parameter is activated to prevent any
possible fault if is necessary to start the
inverter while the motor is running.
0
O
1.
H20-
[Power
On
start]
2.Restart
after
instant
power
failure
3.
Operation
after fault
4.
Normal
accel
Bit 3
Bit 2
Bit 1
Bit 0
0
-
-
-
-
1
-
-
-
2
-
-
-
3
-
-
4
-
-
-
5
-
-
6
-
-
7
-
8
-
-
-
9
-
-
10
-
-
11
-
12
-
-
13
-
14
-
15
1)
: Normal acceleration has first priority. Even though #4 is selected along with other bits, Inverter
performs Speed search #4.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...