13-2
13.2.2 Hardware specification
Item
Specification
Installation
Use S+, S- terminals on control terminal board
Power supply
Use Insulated power from the inverter power supply
13.2.3 Communication specification
Item
Specification
Communication
speed
19,200/9,600/4,800/2,400/1,200 bps selectable
Control procedure
Asynchronous communication system
Communication
system
Half duplex system
Character system
ASCII (8 bit)
Stop bit length
Modbus-RTU: 2 bit ES Bus: 1 bit
Sum check
2 byte
Parity check
None
13.3 Installation
13.3.1 Connecting the communication line
Connect the RS485 communication line to the inverter’s (S+), (S-) terminals of the control terminals.
Check the connection and switch the inverter ON.
If the communication line is connected correctly, set the communication-related parameters as
following:
DRV-03 [Drive mode]: 3(RS485)
DRV-04 [Freq. mode]: 7(RS485)
I/O-60 [Inv. Number]: 1~250 (If more than 1 inverters are connected, be sure to use different numbers
for each inverter)
I/O-61 [Baud-rate]: 3 (9,600 bps as Factory default)
I/O-62 [Lost Mode]: 0 - No action (Factory default)
I/O-63 [Time-Out]: 1.0 sec (Factory default)
I/O-59 [Comm. Prot]: 0 - Modbus-RTU, 1 – ES BUS
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...