9-6
Frequency setting via RS 485 communication
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive
group
0.0
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
7
0 ~ 8
0
Select 7 in Frq code of Drive group.
Related codes: I59, I60, I61
Refer to Chapter 13. RS485 communication.
Frequency setting via Digital Volume (up-down)
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive
group
0.0
[Frequency Command]
-
0 ~400
0.00
Hz
Frq
[Frequency Mode]
8
0 ~ 8
0
Select 8 in Frq code of Drive group.
Related codes: I17 ~ 24.
Among the multifunction inputs (P1 ~ P8), select two terminals to be used for up-down.
Refer to Chapter 7, I/O 2 Group.
Analog Hold
Group
Code
Parameter Name
Setting Range
Initial
Unit
Drive
group
Frq
[Frequency Mode]
2 ~ 7
0 ~ 7
0
I/O group I17
[Multi-function input terminal
P1 define]
-
0 ~ 29
0
~
~
I24
[Multi-function input
terminal P8 define]
23
7
It is available when Frq code setting is 2 ~ 7.
Select one terminal to be used for Analog Hold command among Multi-function input
terminal (P1 ~ P8).
When P8 terminal is selected,
Frequency
P8
Run command
Set freq.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...