10-26
10.9 Sensorless Vector Control
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
group 2
H40
[Control mode select]
3
0 ~ 3
0
-
H30
[Motor type select]
-
0.2 ~ 7.5
-
kW
H32
[Rated
slip frequency]
-
0 ~ 10
-
Hz
H33
[Motor rated current]
-
0.5 ~ 50
-
A
H34
[Motor No Load Current] -
0.1 ~ 20
-
A
H42
[Stator resistance (Rs)]
-
0 ~ 14
-
Ω
H44
[Leakage inductance
(L
σ
)]
-
0~300.00 -
mH
Function
group 1
F14
[Time for energizing a
motor]
-
0.0~60.0
1.0
sec
If H40 – [Control mode select] is set to 3, Sensorless vector control will become active.
CAUTION:
Motor parameters should be measured for high performance. It is highly recommended H41 –
[Auto tuning] be done prior to proceeding operation via Sensorless vector control.
Ensure that the following parameters are entered correctly for high performance in Sensorless vector
control.
H30: Select motor type connected to inverter output.
H32: Enter rated slip frequency, (See chapter 10-6).
H33: Enter motor nameplate rated current.
H34: After removing the load, select H40 – [Control mode select] to 0 {V/F control} and run the motor at
50Hz. Enter the current displayed in Cur-[Output current] as motor no load current. If it is difficult to
remove the load from the motor shaft, enter the value either 40 to 50% of the H33 – [Motor rated current]
or the factory default.
In case that torque ripple occurs at high speed, lower H34 [No load current] to 30%.
H42, H44: Enter the value of the parameter measured during H41 – [Auto tuning] or the factory default.
F14: Is the set time needed to magnetize which will run after this time. A low value set in F14 reduce the
output available torque. The amount of the pre-exciting current is set in H34- [Motor no load current].
Directly enter the motor nameplate values except when 0.2kW motor is used.
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...