10-46
Follow the table below to change the password. (Current PW: 123
→
New PW: 456)
Step
Note
Keypad display
1
Move to H94 code.
H94
2
Press Enter (
) key.
0
3
Enter any number (e.g.: 122).
122
4
Press the Enter (
) key. 0 is displayed because
wrong value was entered. Password cannot be
changed in this status.
0
5
Enter the right password.
123
6
Press Enter (
) key.
123
7
Enter the new password.
456
8
Press the Enter (
) key. Then “456” will blink.
456
9
Press Enter (
) key.
H94
Parameter Lock
Group
Display
Parameter Name
Setting
Range
Default Unit
Function
group 2
H95
[Parameter lock]
-
0 ~ FFFF 0
H94
[Password register]
-
0 ~ FFFF 0
This parameter is used to lock the user-set parameters using the password.
See the table below to lock the user-set parameter via the H94 – [Password Register].
Step
Note
Keypad display
1
Move to H95 code.
H95
2
Press Enter (
) key.
UL
3
Parameter value can be changed in UL (Unlock)
status.
UL
4
Press Enter (
) key.
0
5
Enter the password created in H94 (e.g.: 123).
123
6
Press Enter (
) key.
L
7
Parameter value cannot be changed in L (Lock)
status.
L
8
Press Enter (
) key.
H95
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...