9-22
Skip frequency
Group
Code Parameter Name
Setting Range
Initial
Unit
Function
group 2
H10
[Skip frequency select]
1
0 ~ 1
0
H11
[Skip frequency low limit 1] -
0.1 ~ 400 10.00
Hz
~
~
H16
[Skip frequency low limit 3] -
0.1 ~ 400 35.00
Hz
Set H10 to 1.
Run frequency setting is not available within the skip frequency range of H11-H16.
Skip frequency is settable within the range of F21 – [Max frequency] and F23 – [Start
frequency].
When it is desired to avoid resonance, attributable to the natural frequency of a mechanical system,
these parameters allow resonant frequencies to be skipped. Three different areas of Skip frequency can
be set with the skip frequencies set to either the top or bottom point of each area. However, during
acceleration or deceleration, the run frequency within the set area is valid.
In case of increasing frequency setting as shown above, if frequency set value (Analog setting via
voltage, current, RS485 communication or digital setting via keypad) is within the range of Skip frequency,
it maintains skip frequency low limit value. If the set value is outside the range, it increases the frequency
following the set acceleration ramp.
In case of decreasing frequency setting, if frequency set value (Analog setting via voltage, current,
RS485 communication, or digital setting via keypad) is within the range of Skip frequency, it maintains
Skip frequency high limit value. If the set value is outside the range, it decreases the frequency following
the set deceleration ramp.
Run
command
Freq.
H11
H12
H13
H14
H15
H16
V1(Voltage input)
0
20mA
10V
I (Current input)
Freq. Up setting
Freq. Down
setting
Содержание Sinus M
Страница 10: ......
Страница 15: ...1 5 Notes...
Страница 16: ......
Страница 50: ...6 4 Notes...
Страница 75: ...8 1 CHAPTER 8 CONTROL BLOCK DIAGRAM Frequency setting Drive mode Accel Decel V F control PWM Motor...
Страница 78: ...8 4 Notes...
Страница 114: ...10 14 Normal PID block diagram H54 0...
Страница 115: ...10 15 Process PID block diagram H54 1...
Страница 150: ...10 50 Notes...
Страница 174: ......
Страница 192: ...13 18 Notes...
Страница 204: ......
Страница 208: ...16 4 16 2 Conduit Kit Installation 1 From SINUS M 0001 to SINUS M 0007 2 From SINUS M 0011 to SINUS M 0014...
Страница 217: ...16 13 Model 4000W IP20 A mm B mm L mm H mm P mm 620 600 100 250 40 Overall Dimensions Resistor 4000W IP20...
Страница 219: ...17 1 CHAPTER 17 EC Declaration of Conformity...