70
www.ochsner.com | BA-982018-AIR FALCON-OTS-EN
Factory settings
32. Factory settings
Parameters
Unit
AIR FALCON 212
Target room temperature
standard heating
°C
22
Target room temperature re-
duced heating
°C
20
Target room temperature
standard cooling
°C
24
Target room temperature re-
duced cooling
°C
26
Heating limit
°C
15
Outdoor temperature base
point
(Heating curve)
°C
20
Flow temperature at base
point
(Heating curve)
°C
20
Standard outdoor tempera-
ture
(Heating curve)
°C
-15
Flow temperature at standard
outdoor temperature
(Heating curve)
°C
Low temperature system: 35 / Medium temperature system: 55
Heating curve reference room
temperature
°C
22
Cooling limit
°C
22
Outdoor temperature base
point
(Cooling curve)
°C
20
Flow temperature at base
point
(Cooling curve)
°C
17
Standard outdoor tempera-
ture
(Cooling curve)
°C
32
Flow temperature at standard
outdoor temperature
(Cooling curve)
°C
17
Cooling curve reference room
temperature
°C
24
Target DHW temperature Eco °C
45
Switch-ON differential Eco
K
8
Target DHW temperature
Reduced
°C
43
Switch-ON differential Re-
duced
K
5
Target DHW temperature
Comfort
°C
50
Switch-ON differential Com-
fort
K
4
Target DHW temperature
Boost
°C
55
Target DHW temperature, an-
ti-legionella mode
°C
60
Switch-ON differential, an-
ti-legionella mode
K
5
DHW heat input
kW
5
Bivalent point
°C
0
Target flow temperature man-
ual mode
°C
20
Содержание AIR FALCON 212
Страница 7: ...BA 982018 AIR FALCON sh EN www ochsner com 7...
Страница 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work...
Страница 65: ...OTS_EN www ochsner com 65 Expert mode...
Страница 77: ...OTS_ZSM_EN www ochsner com 77...
Страница 85: ...BA 982018 AIR FALCON EN07 www ochsner com 85...
Страница 86: ...Notes...
Страница 87: ...Notes...