OTS_EN | www.ochsner.com 21
Heating circuit
Note
Low temperature heating systems (e.g. underfloor
heating) react very slowly to changes in the target
room temperature. Due to the additional output
from the system required following the end of a
setback phase, it is possible that the second heat
generator (boiler, electric immersion heater) will cut
in. This can result in higher running costs.
»
Do not set a time program for low temperature
heating, especially for air/water heat pumps.
If you want to select a different operating program not
shown on the main screen, this is possible via the menu.
»
Open the menu.
»
Select the heating circuit for which you want to make
a change.
»
Select “Operating program”.
»
Select “Operating program heating circuit”.
»
Make the required settings.
»
Return to the main screen.
11.3 Setpoints
Different target room temperatures can be set for the dif
-
ferent operating programs. A distinction is made between
the standard target value and the reduced target value.
Note
A change in the target room temperature automat-
ically results in a shift of the heating curve and
cooling curve.
Note
Due to the inertia of the heating system, the effect
of changes to the room temperature settings is al-
ways delayed.
»
Perform only one adjustment per day.
Note
If it is clear that the room temperature does not cor-
respond to your required temperature, especially
at higher or lower outdoor temperatures, we rec-
ommend adjusting the heating curve and cooling
curve accordingly.
(See page 23, Weather-compensated controller)
Note
A change in the target room temperatures also
changes the energy consumption of the heat pump
system.
11.3.1 Heating mode
COMFORT
Parameters
Description
Unit
Target room
temperature
standard heat-
ing
The time program is used to switch
between the following target values in
heating mode:
°C
Target room temperature standard heat-
ing
Target room temperature reduced heating
Target room
temperature
reduced heat-
ing
The time program is used to switch
between the following target values in
heating mode:
°C
Target room temperature standard heat-
ing
Target room temperature reduced heating
Normal mode
Parameters
Description
Unit
Target room
temperature
standard heat-
ing
In heating mode, the temperature is regu-
lated to the target value set here.
°C
Reduced
Parameters
Description
Unit
Target room
temperature
reduced heat-
ing
In heating mode, the temperature is regu-
lated to the target value set here.
°C
11.3.2 Cooling mode
COMFORT
Parameters
Description
Unit
Target room
temperature
standard cool-
ing
The time program is used to switch
between the following target values in
cooling mode:
°C
Target room temperature standard cool-
ing
Target room temperature reduced cooling
Target room
temperature
reduced cool-
ing
The time program is used to switch
between the following target values in
cooling mode:
°C
Target room temperature standard cool-
ing
Target room temperature reduced cooling
Содержание AIR FALCON 212
Страница 7: ...BA 982018 AIR FALCON sh EN www ochsner com 7...
Страница 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work...
Страница 65: ...OTS_EN www ochsner com 65 Expert mode...
Страница 77: ...OTS_ZSM_EN www ochsner com 77...
Страница 85: ...BA 982018 AIR FALCON EN07 www ochsner com 85...
Страница 86: ...Notes...
Страница 87: ...Notes...