54
www.ochsner.com | OTS_EN
Expert mode
Parameters
Description
Unit
Switching dif-
ferential OFF
- room too
warm
When room temperature compensation is
set, the heating circuit switches off if the
room temperature rises above the target
room temperature by the value set here.
K
A
OFF - Room too warm
B
Room temperature
C
Target room temperature
D
Switching differential OFF - room
too warm
E
Heating enabled
A = B > C + D
E = B < C + D/2
Switching
differential
ON - room too
warm
When room temperature compensation
is set, cooling is enabled if the room
temperature rises above the target room
temperature by the value set here.
K
A
ON - Room too warm
B
Room temperature
C
Target room temperature
D
Switching differential ON - room
too warm
E
Cooling enabled
A = B > C + D
E = B < C + D/2
Switching dif-
ferential OFF
- room too cold
When room temperature compensation
is set, cooling switches off if the room
temperature falls below the target room
cooling temperature minus the value set
here.
K
A
OFF - Room too cold
B
Room temperature
C
Target room temperature
D
Switching differential OFF - room
too cold
E
Cooling enabled
A = B < C - D
E = B > C - D/2
OFF - Outage
time
When a heating demand ends, the out-
age time set here must elapse before
cooling is enabled.
min
Room temperature compensation
With this type of control, the target flow temperature is
influenced by the room temperature.
A room temperature
that is too high results in a reduction of the target flow
temperature. A room temperature that is too low results in
an increase in the target flow temperature.
The prerequisite for room temperature compensation is a
valid room temperature, measured by a room temperature
sensor.
If the set heating curve and the room temperature compen-
sation result in a target flow temperature that is lower than
the room temperature, then the target flow temperature
is limited to the current room temperature. Therefore no
more energy is emitted to the room. The room cools down.
Parameters
Description
Room tem-
perature
compensation
correction fac-
tor Kp
This parameter enables the same type of room
temperature compensation as a P controller.
Different guideline values are recommended for
different heating systems. The actual setting must
be made and tested individually.
Setting range
0 - 10
Underfloor heating
0 - 2
Radiator heating
0 - 5
Calculation of the flow temperature in heating mode with
“Room temperature compensation correction factor Kp”
x
= T
RS +
(T
RS
- T
R
) * Kp - T
BZH
k
=
T
VF
- T
VN
T
AF
- T
AN
d
= T
VN
- k * T
AN
T
VL
= k * (T
AG
- x) + d + x
Calculation of the flow temperature in cooling mode with
“Room temperature compensation correction factor Kp”
x
= T
RS
- (T
R
- T
RS
) * Kp - T
BZK
k
=
T
VF
- T
VN
T
AF
- T
AN
d
= T
VN
- k * T
AN
T
VL
= k * (T
AG
- x) + d + x
Formula sym-
bol
Description
Kp
Parameter:
Room temperature compensation correction
factor Kp
T
RS
Target room temperature
T
R
Room temperature
T
BZH
Parameter:
Heating curve reference room temperature
T
BZK
Parameter:
Cooling curve reference room temperature
T
VF
Parameter:
Flow temperature at base point
T
VN
Parameter:
Flow temperature at standard outdoor tempera-
ture
T
AF
Parameter:
Outdoor temperature base point
T
AN
Parameter:
Standard outdoor temperature
T
VL
Flow temperature calculated by controller
T
AG
Average outdoor temperature
Note
If “Room temperature compensation correction
factor Kp”is set to 0, no room temperature com-
pensation will take place.
Содержание AIR FALCON 212
Страница 7: ...BA 982018 AIR FALCON sh EN www ochsner com 7...
Страница 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work...
Страница 65: ...OTS_EN www ochsner com 65 Expert mode...
Страница 77: ...OTS_ZSM_EN www ochsner com 77...
Страница 85: ...BA 982018 AIR FALCON EN07 www ochsner com 85...
Страница 86: ...Notes...
Страница 87: ...Notes...