P5.15
Threshold Detector Delay
Range:
-25.0 to 25.0 s
Default:
0.0 s
If set to a positive value then the Threshold Output does not become On (1) until the input has been above the threshold for the programmed
period of time. If set to a negative value then the Threshold Output remains On (1) until the input has been below the threshold for the programmed
period of time.
Figure 7-16 Threshold Detector - Positive Delay
Figure 7-17 Threshold Detector - Negative Delay
P5.16
Threshold Detector Output Invert
Range:
0 to 1
Default:
0
Set to 1 to invert the logic level from the Threshold Detector.
The Threshold Detector output is shown in bit 2 of
PID Status Indicators
(P1.20).