E172
Fire Mode Error
Fire mode has been deactivated and errors were suppressed while the drive was in fire mode. See
Error History 1
(P1.30)
to
Error History 3
(P1.32).
E189
An In 1 Overload
The input current on T2 analog input 1 has exceeded 24 mA.
Recommended actions:
•
Check control wiring is correct.
•
Check control wiring is undamaged.
•
Check
T2 Analog Input 1 Type
(P6.01)
E190
An In 2 Overload
The input current on T4 analog input 2 has exceeded 24 mA.
Recommended actions:
•
Check control wiring is correct.
•
Check control wiring is undamaged.
•
Check
T4 Analog Input 2 Type
(P6.02)
E216
Firmware Fault 1
Hardware fault - Contact the supplier of the drive.
E220
Firmware Fault 2
Hardware fault - Contact the supplier of the drive.
E222
Firmware Fault 3
Hardware fault - Contact the supplier of the drive.
E224
Firmware Fault 4
Hardware fault - Contact the supplier of the drive.
E228
Ground fault
The drive has detected a ground (earth) fault on the motor cable/windings.
Recommended actions:
•
Check for short circuit to ground (earth) on the output cables
•
Check the integrity of the motor insulation using an insulation tester
E232
Firmware Fault 5
Hardware fault - Contact the supplier of the drive.
E235
Firmware Fault 6
Hardware fault - Contact the supplier of the drive.
E245
Firmware Fault 7
A firmware update has been interrupted.
Recommended Actions:
•
Restart the drive.
•
If the firmware was being downloaded, try again
If the issue persists this could indicate a hardware fault – Contact the supplier of the drive.
E251
Saved Corrupted
This error indicates that parameter data has been corrupted.
Recommended actions:
•
Restore factory defaults (P4.01)
E252
Database Changed
A firmware update has been interrupted. The firmware has been changed but the project parameter values have been lost.
Recommended actions:
•
Restore Factory Defaults (P4.01)