5.5 Understanding the menu structure
The drive parameters, status, and monitoring values can be found within three modes: Status, Parameter Select and Parameter Edit.
Status
The primary mode of the drive that is used to provide users with an indicator to show the current status of the system, see Table 5-2. If the keypad is
to be used to provide a drive frequency reference, the display must be in
Status
for the user to be able to edit the reference using the UP
and
DOWN
buttons. If the drive is running,
Status
will show one of five monitoring parameters and the user can rotate between these by holding the
Settings
button
. The monitoring parameters that can be shown are as follows:
Ramp Output (Hz)
Output Voltage (V)
Output Current (A)
Output Speed (rpm)
Drive Load (%)
Parameter select
From
Status
users can move to
Parameter Select
by pressing the
Settings
button
.
Parameter Select
allows the user to navigate through the drive
parameters. Users can scroll up and down the list of individual parameters by pressing the
UP
and
DOWN
buttons or they can switch between
different menus by holding the
UP
button
to move to the next menu or the
DOWN
button
to move to the previous menu.
Parameter edit
Once the desired parameter has been located in
Parameter Select
, the parameter value can be viewed or edited by pressing the
Settings
button
.
The units of the selected parameter will be shown on the display. To edit the value of the parameter, the
UP
or
DOWN
buttons should be
pressed to increase or decrease the value as appropriate. Holding the
UP
or
DOWN
buttons will move the cursor left or right
respectively. The digit currently being edited will flash.
Status & Monitoring
parameters in Menu 1 are read only and cannot be edited.
Once the change has been made, exit to
Parameter Select
by pressing the
Settings
button
or exit to
Status
by holding the
Settings
button
.
All parameters changes are saved immediately after exiting
Parameter Edit
.
5.6 Saving parameters
Parameter changes are saved automatically after editing by pressing or holding the
Settings
button
to return to
Parameter Select
or
Status
respectively. To save parameter changes over communications,
Save Parameters
(P4.19) should be set to 1. After saving the parameter will reset
to 0.