Communications Diagnostics Technical data
Commander S100 User Guide
23
4.4 Fuse and MCB selection
The fuses and MCBs recommended below are maximum values to protect the recommended cables and prevent noise errors during normal
operation. If smaller cables are used, smaller protection devices may be required.
The voltage rating of fuses and MCBs must be greater than or equal to the highest supply voltage of the system.
Table 4-6 Fuse and MCB selection
* For UL installations, the circuit breaker must be listed under category control number DIVQ / DIVQ7, rated 600 Vac with a short circuit rating > 5 kA.
In other installations, circuit breakers compliant with EN IEC 60947-2 are recommended, with > 5 kA short circuit breaking capacity.
When protected by fuses or circuit breakers with maximum ratings as specified in Table 4-6, this product is suitable for use on a circuit capable of
delivering not more than 5,000 RMS symmetrical amperes, 480 V maximum (up to the rated voltage of the drive module).
Model Number
Rated Current
Rated Power
Supply
Phases
Max supply
Current
IEC*
UL*
Fuses
Class gG
MCB
Type C
Fuses
Class CC, J or T
MCB
Type C
A
kW
hp
A
A
A
100 V Drive (100 to 120 V ±10 %)
S100-01113
1.2
0.18
0.25
1
7.2
10
10
10
15
S100-01123
1.4
0.25
0.33
1
8.5
10
10
15
15
S100-01133
2.2
0.37
0.5
1
10.4
12
12
15
15
S100-03113
3.2
0.55
0.75
1
14.8
16
16
20
25
S100-03123
4.2
0.75
1
1
20.0
25
25
30
25
S100-03133
6
1.1
1.5
1
28.5
32
32
40
40
200 V Drive (200 to 240 V ±10 %)
S100-01S13
1.4
0.18
0.25
1
3.3
6
6
6
15
S100-01213
1.4
0.18
0.25
3
2.0
4
6
6
15
S100-02S11
1.2
0.18
0.25
1
3.3
6
6
6
15
S100-01S23
1.6
0.25
0.33
1
3.8
6
6
6
15
S100-01223
1.6
0.25
0.33
3
2.3
4
6
6
15
S100-02S21
1.4
0.25
0.33
1
3.8
6
6
6
15
S100-01S33
2.4
0.37
0.5
1
4.7
6
6
6
15
S100-01233
2.4
0.37
0.5
3
2.8
4
6
6
15
S100-02S31
2.2
0.37
0.5
1
4.7
6
6
6
15
S100-01S43
3.5
0.55
0.75
1
8.0
10
10
10
15
S100-01243
3.5
0.55
0.75
3
4.7
6
6
6
15
S100-02S41
3.2
0.55
0.75
1
8.0
10
10
10
15
S100-01S53
4.6
0.75
1
1
9.5
12
12
15
15
S100-01253
4.6
0.75
1
3
5.7
8
8
10
15
S100-02S51
4.2
0.75
1
1
9.5
12
12
15
15
S100-01D63
6.6
1.1
1.5
1
15.3
16
20
20
20
3
12.2
16
16
15
15
S100-02S61
6
1.1
1.5
1
15.3
16
20
20
20
S100-01D73
7.5
1.5
2
1
18.4
20
25
25
20
3
14.3
16
16
20
20
S100-02S71
6.8
1.5
2
1
18.4
20
25
25
20
S100-03D13
10.6
2.2
3
1
26.1
32 32
35
30
3
19.7
25
25
25
25
400 V Drive (380 to 480 V ±10 %)
S100-02413
1.2
0.37
0.5
3
1.9
4
6
6
15
S100-02423
1.7
0.55
0.75
3
2.5
4
6
6
15
S100-02433
2.2
0.75
1
3
3.0
4
6
6
15
S100-02443
3.2
1.1
1.5
3
4.5
6
6
6
15
S100-02453
3.7
1.5
2
3
5.6
8
8
10
15
S100-02463
5.3
2.2
3
3
8.2
10
16
15
15
S100-03413
7.2
3
3
3
13.2
16
16
20
15
S100-03423
8.8
4
5
3
16.0
20
20
25
20
Содержание COMMANDER S100