Commander S100 User Guide
79
P3.20
Reverse Motor Direction
Range:
0 to 1
Default:
0 (Normal Operation)
If the motor direction does not match the required forward and reverse control signals, this parameter can be used to change the motor direction
without the need to swap output cables. Changes to this parameter will only take effect when the drive is not running.
This reverses the output phase sequence for the selected forward and reverse directions which is non-standard.
P3.21
Thermal Protection Action
Range:
0 to 4
Default:
3 (Limit with Save)
Set the required thermal protection action as below:
If any of the current limiting modes are selected, both
Motor Thermal Percentage
(P1.22) and
Drive Thermal Percentage
(P1.23) will cause the
current limit to be reduced. If thermal limiting is active, bit 2 is set in
Drive Status Indicators
(P1.10).
P3.22
Low Frequency Thermal Protection
Range:
0 to 1
Default:
1 (On)
If a motor with a shaft mounted fan is likely to run with high loads at low frequencies, then this parameter should be set to 1 (On) to protect the
motor thermally. The drive does this by reducing the level at which it considers the motor to be in overload to 70 % of the motor rated current when
operating below 50 % of the motor's rated frequency.
Figure 7-11 Low Frequency Thermal Protection = On (1)
P3.23
Current Controller Gain
Range:
0 to 250
Default:
40
Used to adjust the gain of the current controller. This does not normally need to be adjusted, but it can be reduced if there is evidence of motor
noise during current limiting. Increasing the value may be required if Standard Ramp (1) or Ramp + Motor Loss (2) are being used in
Deceleration
Ramp Type
(P2.11) with a high inertia load, or if
Supply Loss Action
(P4.08) > 0, as the increased gain will help the control of the D.C. link voltage
during these operations.
NOTE
Value
Thermal Protection Action
Description
0
Disabled
No motor thermal protection but drive thermal protection is still active.
1
Error with Save
Drive generates an Error when Limit reached. Motor and Drive thermal protection
percentages are stored at power down.
2
Error
Drive generates an Error when Limit reached. Motor and Drive thermal protection
percentages start at 0 % at power up.
3
Limit with Save
Current is limited if drive or motor thermal percentage approaches 100 %. Motor and Drive
percentages are stored at power down.
4
Limit
Current is limited if drive or motor thermal percentage approaches 100 %. Motor and Drive
percentages start at 0 % at power up.
70
100
50
Percentage of
Motor Rated
Current (P3.02)
Percentage of Rated Frequency (P3.15)
100
Overload