7.2.2 Menu 2 - Reference & ramps
Parameter
Range
Default
P2.01
Minimum Frequency Limit
0.0 to 300.0 Hz
0.0 Hz
P2.02
Maximum Frequency Limit
0.0 to 300.0 Hz
50Hz: 50.0 Hz
60Hz: 60.0 Hz
P2.03
Frequency Reference Configuration
Custom (0), Local/Remote (1), Voltage/Presets (2), Current/Presets (3),
Presets (4), Keypad (5), Terminal Up/Down (6), Frequency Input (7),
PID Voltage Ref. (8), PID + Feed Forward (9)
Local/Remote (1)
P2.04
Stopping Mode Selector
Coast (0), Ramp (1), Ramp & DC Brake (2), Brake + StopDetect (3),
Timed DC Brake (4) Distance (5)
Ramp (1)
P2.05
S-Ramp Percentage
0.0 to 50.0 %
0.0 %
P2.06
Acceleration Rate 1
0.0 to 1999.9 s
5.0 s
P2.07
Deceleration Rate 1
0.0 to 1999.9 s
10.0 s
P2.08
Acceleration Rate 2
0.0 to 1999.9 s
5.0 s
P2.09
Deceleration Rate 2
0.0 to 1999.9 s
10.0 s
P2.10
Ramp Rate Selector
DI Select (0), Ramp Rates 1 (1), Ramp Rates 2 (2)
DI Select (0)
P2.11
Deceleration Ramp Type
Fast (0), Standard Ramp (1), Standard Ramp + Motor Loss (2)
Standard Ramp (1)
P2.12
Standard Ramp Voltage
0 to DC Bus Voltage (Max) V
Rating Dependent
P2.13
Jog Frequency
±
Maximum Frequency Reference
(P2.02) Hz
1.5 Hz
P2.14
Up/Down Percent Configuration
Reset (0), Last (1), Preset 1 (2), Keypad and Reset (3), Keypad and Last (4),
Keypad and Preset 1 (5)
Reset (0)
P2.15
Up/Down Percentage Time to Max
0 to 250 s
20 s
P2.16
Preset Frequency 1
±
Maximum Frequency Reference
(P2.02) Hz
5.0 Hz
P2.17
Preset Frequency 2
10.0 Hz
P2.18
Preset Frequency 3
25.0 Hz
P2.19
Preset Frequency 4
50.0 Hz
P2.20
Frequency Reference 1 to 4 Selector
Binary (0), Freq. Reference 1 (1), Freq. Reference 2 (2), Freq. Reference 3 (3),
Freq. Reference 4 (4)
Binary (0)
P2.21
Frequency Reference 1 Selector
None (0), Preset 1 (1), Preset 2 (2), Preset 3 (3), Preset 4 (4), T2 Analog 1 % (5),
T4 Analog 2 % (6), T15 Frequency % (7), Up/Down % (8), PID Percent (9)
T2 Analog 1 % (5)
P2.22
Frequency Reference 2 Selector
T4 Analog 2 % (6)
P2.23
Frequency Reference 3 Selector
None (0)
P2.24
Frequency Reference 4 Selector
None (0)
P2.25
Skip Frequency
0.0 to
Maximum Frequency Reference
(P2.02) Hz
0.0 Hz
P2.26
Skip Frequency Band
0.0 to 25.0 Hz
0.5 Hz
P2.27
Fire Mode Reference
±
Maximum Frequency Limit
(P2.02) Hz
0.0 Hz