88
Commander S100 User Guide
P5.12
Threshold Detector Selector
Range:
0 to 15
Default:
0
Selects the input to the threshold detector.
An automatic scaling takes place when parameters are selected as a threshold source such that the threshold input will be at 100 % when the
parameter value is at its maximum.
P5.13
Threshold Detector Level
Range:
0.00 to 100.00 %
Default:
0.00 %
P5.14
Threshold Detector Hysteresis
Range:
0.00 to 25.00 %
Default:
0.00 %
The absolute level of the threshold input selected by
Threshold Detector Selector
(P5.12) is converted to a percentage and compared to the
threshold detector level with hysteresis to determine the detector output. The hysteresis behaviour and levels are described below.
Lower Threshold =
Threshold Detector Level
(P5.13) - (
Threshold Detector Hysteresis
(P5.14) / 2)
Upper Threshold
=
Threshold Detector Level
(P5.13) + (
Threshold Detector Hysteresis
(P5.14) / 2)
Value
Threshold Detector Input
Description
0
None
0 %
1
Ramp Input
The drive frequency reference before the ramps
2
Ramp Output
The drive frequency reference after the ramp has been applied
3
Output Frequency
The output frequency of the drive
4
Output Current
The magnitude of the output current
5
Torque Prod Current
The torque producing output current
6
Output Voltage
The output voltage
7
D.C. Bus Voltage
The D.C. bus voltage
8
T2 Analog 1 %
The value of analog 1 percentage
9
T4 Analog 2 %
The value of analog 2 percentage
10
T15 Frequency %
The value of the frequency input percentage
11
Output Power
The output power
12
Motor RPM
The motor RPM
13
Percentage Load
The percentage load
14
PID Percentage
The percentage output of the PID controller
15
PID Error
The error of the PID controller
Threshold Input
(P5.12) after scaling
Output
Threshold Input < Lower Threshold
Off
Lower Threshold
≤
Threshold Input < Upper Threshold
No change of state
Threshold Input
≥
Upper Threshold
On