Communications Diagnostics Technical data
Commander S100 User Guide
35
T12
Digital Input 2
T13
Digital Input 3
T14
Digital Input 4
Programmable Digital Inputs
T12 Default
Function
Enable
T13 Default
Function
Run Forward
T14 Default
Function
Run Reverse
Function Select
Parameters
T12 Digital Input 2 Function (
P6.17)
T13 Digital Input 3 Function (
P6.18)
T14 Digital Input 4 Function (
P6.19)
Default Logic
Positive Logic
Lower Threshold
< 9 V
Upper Threshold
> 10 V
Absolute
maximum applied
voltage range
-8 V to +30 V relative to 0V
Impedance
6.8 k
Ω
Voltage Range
0 V to +24 V
Sample rate
4 ms
T15
Digital Input 5
Programmable Digital Input or Frequency Input
T15 Default
Function
Ref Switch Bit 0
Function Select
Parameter
T15 Digital Input 5 Function (
P6.20)
Default Logic
Positive Logic
Lower Threshold
< 9 V
Upper Threshold
> 10 V
Absolute maximum
applied voltage
range
-8 V to +30 V relative to 0V
Impedance
6.8 k
Ω
Voltage Range
0 V to +24 V
Sample rate
4 ms
As a Frequency Input
Maximum
Frequency
100 kHz
Low Level
< 5 V
High Level
> 15 V
T41
Relay Normally Open
T42
Relay Common
T43
Relay Normally Closed
Programmable Relay
Relay Default
Function
Drive Healthy
Function Select
Parameter
T41-T43 Relay Function Select (
P6.08)
Contact Voltage
Rating
240 Vac, installation over-voltage category II
Contact Maximum
Current Rating
2 A A.C. 240 V
4 A D.C. 30 V resistive load
0.5 A D.C. 30 V inductive load (L/R = 40 ms)
Minimum
Recommended
Voltage Rating
and Current
12 V 100 mA
Update Rate
10 ms