92
Commander S100 User Guide
P6.05
T15 Digital Input 5 Type
Range:
0 to 1
Default:
0 (Digital Input)
Defines the input type for terminal 15, digital input 5.
T
The frequency input can be scaled, limited and inverted using the associated scaling parameters as described by
T15 Frequency Input Minimum
Input
(P6.29).
The value of this parameter can be set by
Frequency Reference Configuration
(P2.03).
P6.06
T6 Analog Output Function Select
Range:
0 to 17
Default:
2 (Ramp Output)
Selects the output function that the analog output should represent.
Selects the parameter that the analog output should represent. The absolute of the chosen parameter is scaled such that 10 V or 20 mA is
equivalent to the parameter's maximum value. It can be further scaled by
T6 Analog Output Scaling
(P6.07).
P6.07
T6 Analog Output Scaling
Range:
0.000 to 40.000
Default:
1.000
Defines the scaling factor for the analog output.
An automatic scaling takes place when parameters are selected for an analog output such that the analog output will be at full scale when the
parameter value is at its maximum value. Some parameters do not reach their maximum values and so this parameter is provided for the user to
apply further scaling and configure a bigger range of the analog output to be used.
If a scale set here causes the output to exceed 100 %, the output value is limited to 10 V or 20 mA.
Value
Type
Description
0
Digital Input
The low level input must be < 9 V and the high level input > 10 V
1
Frequency Input
Frequency input with a maximum frequency of 100 kHz. The low level input must be < 5 V and the high
level input > 15 V
NOTE
Value
Output Function
Description
0
None
0 %
1
Ramp Input
(P1.13)
The drive frequency reference before the ramps
2
Ramp Output
(P1.14)
The drive frequency reference after the ramp has been applied
3
Output Frequency
(P1.01)
The output frequency of the drive
4
Output Current
(P1.06)
The magnitude of the output current
5
Torque Producing Current
(P1.07)
The torque producing output current
6
Output Voltage
(P1.02)
The output voltage
7
DC Bus Voltage
(P1.24)
The D.C. bus voltage
8
Analog 1 Percentage
(P1.15)
The value of analog 1 percentage
9
Analog 2 Percentage
(P1.16)
The value of analog 2 percentage
10
Frequency Input Percentage
(P1.17)
The value of the frequency input percentage
11
Output Power
(P1.03)
The output power
12
Motor RPM
(P1.04)
The motor RPM
13
Percentage Load
(P1.08)
The percentage load
14
PID Percentage
(P1.19)
The percentage output of the PID controller
15
PID Error
(P1.21)
The error of the PID controller
16
Motor Thermal %
(P1.22)
The thermal percentage to error level of the motor
17
Drive Thermal %
(P1.23)
The thermal percentage to error level of the drive