Running the
motor
Commander S100 User Guide
99
8.1.3 MODBUS registers
The MODBUS register address range is 16 bit (65536 registers) which at
the protocol level is represented by indexes 0 through 65535.
PLC registers
Modicon PLCs typically define 4 register 'files' each containing 65536
registers. Traditionally, the registers are referenced 1 through 65536
rather than 0 through 65535. The register address is therefore
decremented on the master device before passing to the protocol.
The register file type code is NOT transmitted by MODBUS and all
register files can be considered to map onto a single register address
space. However, specific function codes are defined in MODBUS to
support access to the "coil" registers.
All standard CT drive parameters are mapped to register file '4' and the
coil function codes are not required.
Control Techniques parameter mapping
The MODBUS register address is 16 bits in size, of which the upper two
bits are used for data type selection leaving 14 bits to represent the
parameter address.
The table below shows how the start register address should be
calculated.
Data types
The MODBUS protocol specification defines registers as 16 bit signed
integers. All CT devices support this data size.
8.1.4 Data consistency
All CT devices support a minimum data consistency of one parameter
(16 bit or 32 bit data). Some devices support consistency for a complete
multiple register transaction.The Commander S100 only supports 16-bit.
8.1.5 Data encoding
MODBUS RTU uses a 'big-endian' representation for addresses and
data items (except the CRC, which is 'little-endian'). This means that
when a numerical quantity larger than a single byte is transmitted, the
MOST significant byte is sent first. So for example
16 - bits
0x1234
would be
0x12
0x34
8.1.6 Function codes
The function code determines the context and format of the message
data. Bit 7 of the function code is used in the slave response to indicate
an exception.
The following function codes are supported:
FC03 Read multiple
Read a contiguous array of registers. The slave imposes an upper limit
on the number of registers, which can be read. If this is exceeded the
slave will issue an exception code 2.
Table 8-1 Master request
Table 8-2 Slave response
FC06 Write single register
Writes a value to a single 16 bit register. The normal response is an echo
of the request, returned after the register contents have been written.
Table 8-3 Master request
Table 8-4 Slave response
File type
Description
1
Read only bits ("coil")
2
Read / write bits ("coil")
3
Read only 16bit register
4
Read / write 16bit register
Parameter
Protocol register
Decimal
Hex (0x)
m.pp
m x 100 + pp -1
P1.04
103
00 67
P2.20
219
00 DB
P4.19
418
01 A2
Code
Description
3
Read multiple 16 bit registers
6
Write single register
16
Write multiple 16 bit registers
23
Read and write multiple 16 bit registers
43
Read device identification (MEI type 14)
Byte
Description
0
Slave destination node address 1 through 247, 0 is
global
1
Function code 0x03
2
Start register address MSB
3
Start register address LSB
4
Number of 16 bit registers MSB
5
Number of 16 bit registers LSB
6
CRC LSB
7
CRC MSB
Byte
Description
0
Slave source node address
1
Function code 0x03
2
Length of register data in read block (in bytes)
3
Register data 0 MSB
4
Register data 0 LSB
3+byte count CRC LSB
4+byte count CRC MSB
Byte
Description
0
Slave node address 1 through 247, 0 is global
1
Function code 0x06
2
Register address MSB
3
Register address LSB
4
Register data MSB
5
Register data LSB
6
CRC LSB
7
CRC MSB
Byte
Description
0
Slave source node address
1
Function code 0x06
2
Register address MSB
3
Register address LSB
4
Register data MSB
5
Register data LSB
6
CRC LSB
7
CRC MSB