Commander S100 User Guide
73
P2.25
Skip Frequency
Range:
0.0 to
Maximum Frequency Limit
(P2.02)
Default: 0.0
Hz
The skip frequency function is available to prevent continuous operation within a specified frequency range (i.e. where mechanical resonance may
occur).
Skip Frequency Band
(P2.26) defines the range either side of the value set here over which references are rejected in either direction.
Figure 7-7 Skip Frequency set up
P2.26
Skip Frequency Band
Range:
0.0 to 25.0 Hz
Default:
0.5 Hz
Defines the range either side of the skip reference to be skipped. See